• 1-Banner

Xarunta Xogta

  • IDC Rack (Xarunta Xogta Internetka ee Rack)

    IDC Rack (Xarunta Xogta Internetka ee Rack)

    Astaamaha Muhiimka ah & Tilmaamaha:

    Cabbirka: ballaca caadiga ah: 19 inji (482.6 mm) Dhererka: Cutubka Rack 47U Dheef: 1100mm

    Taageer cabbirka gaarka ah sida waafaqsan shuruudahaaga.

    Awoodda Load: Lagu qiimeeyay kiiloogaraam ama rodol. Waa muhiim in la hubiyo in golaha wasiiradu ay taageeri karaan miisaanka guud ee dhammaan qalabka la rakibay.

    Qalabka Dhismaha: Waxaa laga sameeyay bir culus, qabow-duuban oo xoog iyo adkeysi leh.

    Daloolin: Albaabada hore iyo kuwa danbe ayaa inta badan daloola (Meshed) si loogu ogolaado socodka hawada ugu fiican.

    Waafaqid: Waxaa loo qaabeeyey in lagu hayo qalabka caadiga ah ee 19-inch rack-mount.

    Maareynta Cable-ka: Laba fiilooyinka wax gelinta ah oo leh furayaasha CEE 63A, baararka maaraynta fiilooyinka / marinnada faraha si loo habeeyo loona hago shabakada iyo fiilooyinka korantada.

    Qaboojin wax ku ool ah: Albaabada daloolsan iyo baalalku waxay sahlaan socodka hawada saxda ah, taas oo u ogolaanaysa hawo qaboojiye qaboojin oo ka imanaysa nidaamka qaboojinta xarunta xogta si ay u soo dhex maraan qalabka oo ay si fiican u damiso hawada kulul, ka hortagga kulaylka.

    PDU toosan (Cutubka Qaybinta Awoodda): Laba 36 dekedood C39 PDU smart ayaa ku rakiban biraha toosan si ay u bixiyaan meelaha korontada ku dhow ee qalabka.

    Codsiga: Golaha IDC, oo sidoo kale loo yaqaan "Server Rack" ama "Network Cabinet", waa qaab dhismeed la jaan-gooyey, oo xiran oo loogu talagalay in si ammaan ah loo dejiyo loona habeeyo qalabka IT-ga muhiimka ah gudaha Xarunta Xogta ama qolka server-ka ee gaarka ah. "IDC" waxay u taagan tahay "Xarunta Xogta Internetka".

     

  • Miner Rack oo leh 40 Dekadood C19 PDU

    Miner Rack oo leh 40 Dekadood C19 PDU

    Tilmaamaha:

    1. Cabbirka Golaha (W*H*D):1020*2280*560mm

    2. Cabbirka PDU (W*H*D):120*2280*120mm

    Voltage Input: saddex waji 346 ~ 480V

    Soo Gelida Hadda: 3*250A

    Korontada wax soo saarka: hal-waji 200 ~ 277V

    Outlet: 40 dekedood ee C19 Sockets oo loo habeeyey saddex qaybood

    Deked kastaa waxay leedahay 1P 20A wareegga wareegga

    Qalabkayaga macdan qodista waxa uu leeyahay C19 PDU oo si toosan ugu rakiban dhinaca qaabaynta qaabaysan, meel-badbaadin iyo qaab xirfadeed.

    Nadiifi, habaysan oo loo habeeyay waxqabadka ugu sarreeya.

  • 2500A Golaha Qaybinta Korontada Dibadda

    2500A Golaha Qaybinta Korontada Dibadda

    Qeexitaanka Sabuuradda:

    1. Voltage: 415V/240 VAC

    2. Hadda: 2500A, 3 Waji, 50/60 Hz

    3. SCCR: 65KAIC

    4. Qalabka Golaha: SGCC

    5. Ku-xiran: NEMA 3R bannaanka

    6. MCCB ugu weyn: Noark 3P/2500A 1PCS

    7. MCCB: Noark 3P/250A 10PCS&3P/125A 1PCS

    8. 3 mitirka awoodda muti-function ee wajiga

  • HPC 36 PORTS C39 SMART PDU

    HPC 36 PORTS C39 SMART PDU

    Tilmaamaha PDU

    1.Input danab: 346-415VAC

    2. Gelitaanka hadda: 3 x 60A

    3. Korontada wax soo saarka: 200 ~ 240VAC

    4. Outlets: 36 dekedood ee saldhigyada C39 oo leh muuqaal is-quful ah Socket ku habboon C13 iyo C19 labadaba

    5. Xarumo loo habeeyey isku xigxiga waji kale oo madow, casaan, buluug ah

    6. Ilaalinta: 12 pcs of 1P 20A UL489 hydraulic magnetic circuit breakers Hal jabiye saddexdii gooboodba

    7. Kormeeraha fog ee PDU gelinta hadda, danab, awood, KWH

    8. La soco meel fog ka kasta oo wax soo saarka dekedda hadda, danab, xoog, KWH

    9. Smart Meter oo leh interface Ethernet/RS485, taageer HTTP/SNMP/SSH2/MODBUS

    10. Bandhig LCD oo korkiisa ah oo leh koontarool menu iyo kormeer maxalli ah

    11. Heerkulka deegaanka ee shaqaynaya 0 ~ 60C

    12. UL/CUL Liiskaan oo La Xaqiijiyay (ETL Mark)

    13. Terminalka wax-gelinta waxa uu leeyahay 5 X 6 AWG xariiq 3 mitir ah

  • HPC 24 PORTS C39 SMART PDU

    HPC 24 PORTS C39 SMART PDU

    Tilmaamaha PDU:

    1. Voltage Input: 346-415V

    2. Input current: 3*125A

    3. Korontada soo baxda: 200-240V

    4. Outlets: 24 dekedood oo ah saldhigyada C39 oo leh muuqaal is-quful ah Socket ku habboon labada C13 iyo C19

    5. Ilaalinta: 24pcs of 1P20A UL489 circuit breakers Hal jabiye ee meel kasta

    7. Kormeeraha fogaanta ee PDU iyo mid kasta oo deked ah hadda, danab, koronto, KWH

    8. La soco meel fog ka kasta oo wax soo saarka dekedda hadda, danab, xoog, KWH

    9. Smart Meter oo leh interface Ethernet/RS485, taageer HTTP/SNMP/SSH2/MODBUS

    10. UL/CUL Liiskaan oo la xaqiijiyay